UL Catalog 2022-2023 - Flipbook - Page 33
SPECIFICATIONS
General
• Variable speed models are available in variable lengths only.
• Fixed speed models are available in variable length and fixed
length options.
• Max. liquid viscosity: 70 SSU at 60 °F (15 °C).
• STP variable speed models are UL and cUL listed for fuel
mixtures containing up to 10% ethanol, and 20% MTBE, 20%
ETBE or 17% TAME with gasoline.
• Pressure relief valve: available in four pressure relief settings,
integral to check valve. Standard model relieves at 40 psi and
resets above 35 psi.
• STPAG (AG compatible) models are UL listed for fuel mixtures
containing diesel fuel with up to 20% Biodiesel, 100%
Biodiesel, up to 85% ethanol with gasoline, and 20% MTBE,
20% ETBE or 17% TAME with gasoline.
• Syphon: venturi-type syphon primer supplied with every
submersible. Syphon check valve and secondary syphon sold
separately.
• All variable speed (non-AG) models can also be used with
diesel fuels, fuel oils, kerosene, Avgas and jet fuels in a
non-gelled pourable state.
• Air eliminator: every submersible includes a tank return path
with one-way check valve to provide active air elimination.
• 2 Hp fixed speed models can also be used with diesel fuels,
fuel oils, kerosene, Avgas and jet fuels in a non-gelled
pourable state.
• Electrical disconnect: electrical yoke for positive contractor
disconnect during service.
Variable Speed Pump Motor
• 2 Hp, variable speed, two-stage centrifugal type pump motor
with integral, automatic, thermal overload protection.
• Max. pressure: selectable operating pressure on MagVFC™
between 24 psi and 42 psi deadhead.
• Available with MagShell® which results in 45% increased flow
area around motor.
Fixed Speed Pump Motor
• 2 Hp fixed speed, 3450 rpm, multi-stage centrifugal
type pump motor with integral, automatic, thermal
overload protection.
• All wetted elastomers are made of a high grade, fluorocarbon
compound.
Variable Speed Power Requirements
• Variable speed pumps can only be controlled by a MagVFC™
variable frequency controller.
• VS2 models can operate with single- or three-phase incoming
power supply to the MagVFC™.
• Incoming power supply to the MagVFC™ can be 200-250 VAC,
50 or 60 Hz.
• MagVFC™ outputs a three-phase, variable frequency signal,
valid for FE PETRO® variable speed pumps only.
• MagVFC™ max. line draw: 20 Amps.
• Standard pressure (M200, two-stage) model, max.
pressure = 36 psi.
• Max motor draw: 7 Amps.
• High pressure (HM200, three-stage) model, max.
pressure = 45 psi.
Fixed Speed Power Requirements
• Available with MagShell™ for 45% increased flow area
around motor.
Approvals
• cULus listed.
• Consult factory for applicable approvals.
SUBMERSIBLE
PUMPING SYSTEMS
• Check valve: 2¾" diameter fluorocarbon seal constructed
with cast aluminum body and steel backing washer.
Liquid Compatibility
• 2 Hp fixed speed models require single-phase, 208-230 VAC,
60 Hz incoming power.
• 2 Hp fixed speed models incorporate a starting and running
capacitor, with internal bleed resistor, rated 370 Volt, 40
microfarad.
• SPGC-220 single-phase Guardian Series™ Controllers and
STP-CBS single-phase control boxes are available for 2 hp
pump control.
• Max. motor draw: 12 Amps.
33