Gozney Master 75 x 75 Manual - V1.8 - Flipbook - Page 18
PRE-INSTALL
VENTING
GAS CLOSURE VENTILATION
It is important that the gas burner has sufficient ventilation to
operate correctly.
Gas ovens require clearance air spaces to ensure the gas
burner has adequate air intake. It is necessary to create an air
intake opening, measuring at least 500 mm x 500 mm, located
underneath the oven door/opening, as shown in the diagrams
above. Doing so will ensure that the air required for the gas
burner will be taken from the same atmospheric environment in
which the oven chamber opens. This is required for optimum
gas burner operation.
WARNING: Ensure the air intake opening remains clear from
obstruction at all times. When installing the oven outdoors, the
area around and beneath the oven must be kept clear of grass,
leaves and other combustible materials at ALL times.
Allow vent
Cladding to customers
design
Correct gas enclosure
OVEN SUPPORT STAND ENCLOSURE
In order for the gas burner to operate correctly, the external walls
of the oven support stand must be enclosed on all sides to shield
the gas burner from drafts or other atmospheric interruptions.
Support stand enclosure must be made entirely from noncombustible materials.
Incorrect gas enclosure
18